 AC/DC POWER HiTESTER 3334 POWER HiTESTER 3333
Power Measuring Instruments
By Popular Demand
Ideal for Meeting Energy Efficiency Standards
High Accuracy & Cost Performance All in One Device Choose the 3334 for DC and Current/Power Integration Applications
3334

High Accuracy (0.1% rdg. 0.1% f.s. for 1 year)
Exceeds the 0.5% accuracy benchmark stipulated by international standards.
Extended Period of Guaranteed Accuracy of 3 Years
Calibration expenses are reduced by a calibration interval six times that of our former models.
Maximum Cost Performance
All the necessary functions and accuracy requirements are provided in an easy-to-use, no-frills device.
3333
2
The HIOKI AC/DC POWER HiTESTER Solves All of
All the Features for DC and Current/Power Integration Measurements
3334 AC/DC POWER
Complete Accuracy Over a Wide Input Range
1.00mA 0.150V 0.0000W
Current: 1mA to 30A, Voltage: 0.15V to 300V, Apparent Power: 0W to 9kW
All Measurements Within this Range Fully Guaranteed for Accuracy
30.00A 300.0V 9.000kW
Measure AC or DC Loads
Capture
With a DC to 5kHz frequency bandwidth, all AC and DC measurement and AC/DC elements such as half-wave rectified values can be tested reliably and accurately [AC+DC Mode]: For half-wave rectified loads common in small household appliances such as hair dryers [DC Mode]: For pure DC loads in batteries [AC Mode]: For loads in commercial power lines powering common household appliances
Switch modes simply by pressing the DC/AC button on the panel
Half-wave rectified
0.0 A
Inrush Current with the Peak Measurement Function
Measure for the Peak Value of Voltage and Current for Each Polarity Indepedently. Also measure the inrush current or surge current of electrical equipment.
Measure simply by pressing the SHIFT+HOLD keys.
inrush current
Measure the inrush current when copiers and similar equipment are started
peak current
All waves rectified
0.0 A
Some hair dryers operate by switching the output by a half-wave rectified.
Measure the peak current of the standby power of home entertainment devices
80% of Actual Size Shown
Intuitive
Setting Procedures and Easy-to-Understand Displays
Both the 3333 and 3334 offer simple operating procedures and quick and easy-to-understand readings and alarm displays. Settings can be made for obtaining the average of captured data (AVG), VT ratio (conversion ratio), CT ratio, GP-IB address, integration time (from 1 minute to 10,000 hours), and D/A Output Parameters. Information regarding the Power HiTESTER's currents status such as display hold, remote control settings, and key lock (to prevent unauthorized reconfigurations) can be viewed at a glance. *Easily test for over-consumption even when testing distorted waveforms that are commonly found in switching power supplies and similar devices by monitoring for the [PEAK OVER] alarm, simply by setting for the alarm to activate and the display to light up when the input exceeds the range.
3
your Energy Consumption Testing Needs
Meet Industrial Standard Requirements for Test Accuracy Measure for Consumed Power
Also ideal for measuring the standby power and power consumption level of household appliances
AC/DC Current and Power Integration
Even measure the discharge level of each individual polarity of batteries
Accurate
Even for Waveforms with Large Crest Factors
Reliably test waveforms with large crest factors (peak value with respect to the RMS value) such as pulsed systems
*Highest effective peak voltage and peak current values on the 3334 are 300% of the range. Accuracy is guaranteed for 1% to 100% of both ranges.
300mA peak to peak
Measure the amount of solar generated power and how much is being sold back to the power company
Devices that are highly vulnerable to power fluctuations such as copiers and cycle-controlled equipment can also be measured for integrated power
For example, in the 100mA range where the RMS value= 1mA Peak value= 300mA, CF=300 Even waveforms such as this can be measured accurately with the 3334.
1mA rms
Universal
Power Supply
Easy-to-connect Terminals
Make a secure connection with the screw-type terminals
*Use a No.3 Phillips screwdriver Actual Size
Compatible to 100 - 240V AC Power Supplies
Small
Footprint
Leading edge technology and innovations helped to minimize the space required, while still enabling DC measurements.
*Standard rack mount kits also available upon special order. Rear Panel Design of Model 3334-01 with built-in GP-IB Interface
210
Analog
Output on All 4 Channels
Voltage Current Active power
*Simultaneously ouput the voltage, current and active power values (DC 2 V f.s., data refreshed 5 times/second) *Output the apparent power, power factor, or integrated current/active power over an additional 1 channel
100
15
Integrated active power
Waveform
Output over 3 Channels
Voltage
Data
management with PC
Instantaneous waveforms of Waveform of a motor startup the measured voltage, current and active power can be simultaneously output *Output: 1 V f.s. *Sampling speed: 74.4kHz
(at 50Hz: 1488 points/waveform) (at 60Hz: 1240 points/waveform)
Ask your distributor for more information regarding the freeware for processing your measurement data
Make full use of these interfaces to increase efficiency *RS-232C (3334) *RS-232C, GP-IB (3334-01)
Current
Active power
4
Fully Answering the Needs for a High Accuracy, Long-lasting, and User-
Accuracy That Can Only Be Realized with a Digital Display
3333 AC POWER
Multifunctional - 3 Meters In One
Selectable simultaneous display of voltage, current, power (active or apparent) or power factor Display a: voltage, current or active power Display b: current, active power or apparent power Display c: active power, power factor, voltage or current
Operation: Press the a, b or c key to switch between parameters
Quick and Simple Settings
Easy-to-see display
Press the SET key to display settings Display a: AVG setting (number of samples to average) convenient for displaying severely fluctuating values Display b: VT (voltage transformer) ratio setting Display c: CT (current transformer) ratio setting To expand the measurement input level, VT and CT ratios can be set for transformer measurements. Primary winding input values can be read directly.
Operation: Press NEXT or the a, b or c key to select a setting item
Bright emissive numeric and unit symbol display
Actual Size
Clearly visible instrument status
Display hold, remote control and key-lock states are indicated separately.
Check for Errors at a Glance
Warning lights indicate out-of-range input to Model 3333 when measuring voltage and current of distorted waveforms, such as in power switching circuits.
Easy range setting
Convenient functions
1. Key Lock (SHIFT + KEY LOCK keys) Useful for avoiding inadvertent operations on production lines. 2. Data Print (SHIFT + DATA OUT keys) Obtain hard copies of measurement data using the optional Printer Model 9442.
Select current range simply by pressing the button (accepts up to 30 AAC, including auto-ranging) No voltage range setting required (accepts up to 300 VAC)
5
Friendly Power Measuring Device for the Production and Inspection Lines
Model 3333 Measurement accuracy: 0.5% rdg. or better Period of guaranteed accuracy (Recommended calibration interval): 3 years Easy Operation Digital Display Data management on a PC Cost-Performance What are the advantages? Model 3333 fully exceeds the accuracy level of traditional analog meters that has an accuracy of only 0.5% f.s. 0.5% f.s is assured for a full three years, reducing calibration costs and production time losses Gone is the need to check for zero-position before measurement as you would on traditional analog meters 7 210 261 30 Quickly grasp the measurement data at a glance Facilitate reporting and data recording needs using your computer Take care of a multitude of measurement needs with a single low-cost instrument
Universal Power Supply
Easy-to-connect Terminals
210
7
15
100
261
34
Compatible to 100 - 240V AC Power Supplies
*Be sure to use a No. 3 Phillips screwdriver (available as an optional accessory) to loosen and secure the screws. Actual Size
Space-saving footprint
Smaller installation space. The installed footprint of the POWER HiTESTER 3333 is about 34% smaller than that of former models. This size reduction makes the instrument especially easy to install.
Rear Panel Design of Model 3333-01 with built-in GP-IB Interface *Rack mounts for various installations also available on special order. Please inquire for details.
160
Three-channel analog output
Voltage, current and active power measurements are simultaneously output as +2 VDC f.s. levels (refreshed about five times per second).
15
Screw-in terminal block affixes wires securely. Because bad wiring connections can present a fire hazard, the screw-type terminal block has been incorporated to ensure secure wiring.
100
100
15
Connect to Printer Model 9442
PC measurement and data management
Use the optional Printer Model 9442 to print without concern for troublesome settings.
RS-232C interface built-in Select Model 3333-01 for additional built-in GP-IB interface
6
3334 and 3333 Specifications
3334 (AC/DC) General Specifications
Measurable lines Single-phase, 2-wire (AC/DC) Single-phase, 2-wire (AC) Voltage, current, active power, apparent power, power factor, Voltage, current, active power, apparent power, power factor Measurement parameters frequency, integrated current and active power, waveform peak (voltage and current) Measurement method Sampling Frequency Measurement Range Simultaneous digital sampling of voltage and current, True RMS Approximately 74.4kHz Switch between auto-range or manual 200.0V 50.00m/ 200.0m/ 500.0m/ 2.000/ 5.000/ 20.00A 45Hz to 5kHz Approximately 48kHz
3333 (AC)
Voltage 15.000/ 30.00/ 150.00/ 300.0V Current 100.00m/ 300.0m/ 1.0000/ 3.000/ 10.000/ 30.00A Frequency bandwidth DC, 45Hz to 5kHz
Power 1.5000W to 9.000kW (refer to range composition table below) 10.000W to 4.000kW (refer to range composition table below) Guaranteed at 23C5, max. 80%rh, sine wave input, power factor=1, in-phase voltage =0V (accuracy specifications differ depending on usage period of 1 or 3 years) 3 minutes 10 minutes Voltage, current, power: 10% to 150%
Accuracy
Warm-up time
Period of guaranteed accuracy 3 years (better accuracy specifications available for 1-year period) Effective measurement range Voltage, current:1% to 100% (Power: 0% to 100%) Effect of power factor (at pf=0.5) Maximum 0.4%rdg. (45 to 66Hz) Temperature Coeffi cient Maximum 0.03%f.s./C Values in the ( ) represent the effective measurement range Measurements below 0.5% of the voltage or current range will be zero suppressed.
(0.0100 to 1.0000A) (0.000 to 15.000W) (0.00 to 30.00W) (0.00 to 150.00W) (0.0 to 300.0W)
Measurement ranges - Model 3334
Current Voltage (0.150 to 15.000V) (0.30 to 30.00V) (1.50 to 150.00V) (3.0 to 300.0V) (1.00 to 100.00mA) (0.0000 to 1.5000W) (0.000 to 3.000W) (0.000 to 15.000W) (0.00 to 30.00W)
100.00mA 1.5000W 3.000W
(3.0 to 300.0mA) (0.000 to 4.500W) (0.000 to 9.000W) (0.00 to 45.00W) (0.00 to 90.00W)
300.0mA 4.500W 9.000W 45.00W 90.00W
1.0000A
(0.030 to 3.000A) (0.00 to 45.00W) (0.00 to 90.00W) (0.0 to 450.0W) (0.0 to 900.0W)
3.000A
(0.100 to 10.000A) (0.00 to 150.00W) (0.0 to 300.0W) (0.0000 to 1.5000kW) (0.000 to 3.000kW)
10.000A
(0.30 to 30.00A) (0.0 to 450.0W) (0.0 to 900.0W) (0.000 to 4.500kW) (0.000 to 9.000kW)
30.00A
15.000V 30.00V
15.000W 30.00W
45.00W 90.00W 450.0W 900.0W
150.00W 300.0W
450.0W 900.0W
150.00V 300.0V
15.000W 30.00W
150.00W 300.0W
1.5000kW 3.000kW
4.500kW 9.000kW
Measurement ranges - Model 3333
Current Voltage (20.0 to 300.0V) (5.00 to 75.00mA) (1.000 to 15.000W)
Values in the ( ) represent the effective measurement range Measurements below 0.5% of the voltage, current , or power range will be zero suppressed.
(50.0 to 750.0mA) (10.00 to 15.00W)
50.00mA 10.000W
(20.0 to 300.0mA) (4.00 to 15.000W)
200.0mA 40.00W
500.0mA 100.00W
(0.200 to 3.000A) (40.0 to 600.0W)
2.000A
(0.500 to 7.500A) (0.1000 to 1.5000kW)
5.000A
(2.00 to 30.00A) (0.400 to 6.000kW)
20.00 A
200.0V
400.0W
1.0000kW
4.000kW
Measurement accuracy - Model 3334
Frequency
Guaranteed Period Voltage, current and active power (at less than 50% of input range) Current and active power (at 50% to 100% of input range)
Notes
1 year 0.1%rdg.0.2%f.s. 3 years 0.1%rdg.0.35%f.s. 1 year 0.1%rdg.0.1%f.s. 0.2%rdg. 45 Hz f 66 Hz 3 years 0.1%rdg.0.2%f.s. 0.3%rdg. 1 year 0.1%rdg.0.2%f.s. 0.3%rdg. 66 Hz < f 1 kHz 3 years 0.1%rdg.0.35%f.s. 0.45%rdg. 1 year 3.0%f.s. 3.0%rdg. 1 kHz < f 5 kHz 3 years 4.5%f.s. 4.5%rdg. *Add 50A to the accuracy when measuring DC current *Add (50A x voltage value) to the accuracy when measuring DC active power DC
Guaranteed Period Voltage, current and active power (input current 20 A or less) Current and active power (input current over 20 A)
Accuracy not defined for c u r re n t i n p u t exceeding 20A
3334 and 3333 Arithmetic Expressions Measurement Formula Parameters Apparent Power S=UxI (S) Power Factor () =P/S (Sum of I from start of integration) Integrated Current (1 hour of data) Integrated Active (Sum of P from start of integration) Power (1 hour of data) *U=Tested Voltage Value, I=Tested Current Value, P=Tested Active Power Value Calculating precision is 1dgt. against the results obtained from each measured value Current and active power integration available only on Model 3334.
Measurement accuracy - Model 3333 Values in the ( ) indicate accuracy when input exceeds 100% of range.
Frequency Notes
45 Hz f 66 Hz 66 Hz < f 1 kHz 1 kHz < f 5 kHz
1 year 3 years 1 year 3 years 1 year 3 years
0.1%rdg.0.1%f.s. (0.2%rdg.) 0.1%rdg.0.2%f.s. (0.3%rdg.) 0.1%rdg.0.2%f.s. (0.3%rdg.) 0.1%rdg.0.35%f.s. (0.45%rdg.) 3.0%f.s. (3.0%rdg.) 4.5%f.s. (4.5%rdg.)
Accuracy not defined for c u r re n t i n p u t exceeding 20A
7
3334 (AC/DC) Input
Input impedance Maximum input voltage Maximum input current 2.4 M for voltage, 10 m or better (50/60 Hz) for current 300V, 425Vpeak 30 A, 42.5 Apeak
3333 (AC)
2.4 M for voltage, 7 m or better (50/60 Hz) for current 300 Vrms, 425 Vpeak 30 Arms, 42.5 Apeak Within 425Vpeak 300% of each current range, Within 42.5Apeak 300V (50/60Hz) voltage and current: 1% to 152% of range active power: 0% to 231.04% of range
Maximum effective peak voltage 300% of each voltage range, Within 425Vpeak Maximum effective peak current 300% of each current range, Within 42.5Apeak Max. rated voltage to earth 300V (DC, 50/60Hz)
Display
Display indication range Displacement power factor Display refresh rate Response time voltage and current: 0.5% to 105% of range active power: 0% to 110.25% of range 0.000 to 1.000 (no polarity display) approx. 5 times per second within 0.5 s (time to rated accuracy after abrupt change in input [0 to 90% or 100 to 10% of range]) No.of displayed digits: Six digits Current Integration: form 0.00000mAh, Polarity-independent integration and Sum value Active power Integration: form 0.00000mWh, Polarity-independent integration and Sum value Integration time: 1 min to 10000 h Measurement accuracy: measurement accuracy of active power 1dgt. Maximum value of positive and negative waveform of voltage/ current (up to 300% of full scale range) Measurement accuracy: 1.2%f.s. ("f.s." is 300% of each range) Switchable between AC+DC(True RMS), DC(simple average display) and AC(True RMS) Parameter output representation: voltage, current and active power (3 simultaneous channels) D/A select an item from current integration, active power integration, apparent power, power factor Voltage output: 1 VDC f.s. for each range Output accuracy: 0.5% f.s. + individual measurement accuracy Parameter output representation: voltage, current and active power (3 simultaneous channels) Voltage output: 1 VDC f.s. for each range Output accuracy: 1.0% f.s. + individual measurement accuracy
Functions
Integration measurement
Wave peak measurement Rectification method
AC(True RMS) Parameter output representation: voltage, current and active power (3 simultaneous channels) Voltage output: +2 VDC f.s. for each range Output accuracy: 0.5% f.s. + individual measurement accuracy
Analog output (D/A output)
Waveform output
Average function
VT or CT ratio
Simple averaging of specified number of samples: 1, 2, 5, 10, 25, 50 or 100 VT ratios: 1, 2, 4, 10, 20, 30, 60, 100 VT ratios: 1, 2, 4, 10, 20, 30, 60, 100 CT ratios: 1,2,3,4,5,6,8,10,12,15,16,20,24,25,30,40,50,60, CT ratios: 1,2,3,4,5,6,8,10,12,15,16,20,24,25,30,40,50,60, 75, 80,100,200,300,500,1000,2000,3000,5000, 75,80,100 10000 RS-232C interface: included as standard, Asynchronous communication method: full-duplex; Baud rate: 9600 bps (fixed) GP-IB interface: Model 3334-01 only GP-IB interface: Model 3333-01 only IEEE-488.1 1987 compliant, IEEE-488.2 1987 reference IEEE-488.1 1987 compliant, IEEE-488.2 1987 reference Display Hold (HOLD), Maximum value hold, Peak value hold, Display Hold (HOLD), Key Lock (KEYLOCK), Key Lock (KEYLOCK), Backup function (preserves settings, Settings backup (preserves settings) integration data)
External Interfaces
Miscellaneous
General Specifications
Safety EMC Operating environment Storage environment Rated supply voltage Maximum rated power Size and weigh EN61010-1:2001 Pollution Factor 2, Measurement Category III (4000 V anticipated overvoltage) EN61326, EN61000-3-2, EN61000-3-3 0 to 40 C, 80% RH or less, non-condensating -10 to 50 C, 80% RH or less, non-condensating 100 to 240 VAC, 50/60 Hz 20 VA 210W x 100H x 245D mm (excluding feet and projections), 160W x 100H x 227D mm (excluding feet and projections), 2.5 kg 1.9 kg
8
Operate
the Power HiTESTER from Your PC
Data Management is as Easy as 1-2-3
RS-232C (built-in with the 3334 and 3333) RS-232C, GP-IB (built-in with the 3334-01 and 3333-01) Free RS-232C application for both models available from your authorized HIOKI distributor only.
*Features and Functions
1. Operate the Power HiTESTER's keys on the PC as you would on the actual unit 2. Further process test data on spreadhseet software such as Excel
Use of the software require a comprehensive understanding of the protocols and commands. Support for modifications to the software not available.
3334
3333
AC/DC POWER HiTESTER 3334 POWER HiTESTER (with GP-IB) 3334-01
(Accessories: Instruction Manual (1), Power cord (1))
POWER HiTESTER 3333 POWER HiTESTER (with GP-IB) 3333-01
(Accessories: Instruction Manual (1), Power cord (1))
Options (Common to both Models 3334 and 3334-01)
RS-232C CABLE (9-pin to 9-pin, crossed cable/1.8m(0.07ft)) 9637 RS-232C CABLE (9-pin to 25-pin, crossed cable/1.8m(0.07ft)) 9638 GP-IB CONNECTOR CABLE (2m) 9151-02 GP-IB CONNECTOR CABLE (4m) 9151-04 No. 3 Phillips screwdriver
RS-232C CABLE 9637
GP-IB CONNECTOR CABLE 9151-02
No. 3 Phillips screwdriver
Option Printer (For the 3333 and 3333-01)
PRINTER 9442 CONNECTION CABLE (for printer 9442) 9444 RECORDING PAPER 1196 AC ADAPTER (for printer 9442 operation in Europe, except Switzerland) 9443-02 AC ADAPTER (for printer 9442, for USA) 9443-03
Print method : Thermal serial dot printing Paper width : 112 mm(4.41ft) Power supply : 9443-02/03 AC adapter, or supplied nickel-metal hydride battery Dimensions and weight : 160W(6.30")x 66.5H(2.62") x 17D(0.67") mm, 580g(20.5oz.)
CONNECTION CABLE 9444
AC ADAPTER 9443-02
When purchasing the Printer 9442, make sure you also purchase the Connection cable 9444 and AC adapter 9443-02/03 so that you can connect it to the 3333/3333-01.
1904 Shanghai Times Square Office, 93 Huai Hai Zhong Road Shanghai, P.R.China POSTCODE: 200021 TEL +86-21-6391-0090/0092 FAX +86-21-6391-0360 E-mail: info-sh@hioki.cn
HIOKI (Shanghai) Sales & Trading Co., Ltd. :
DISTRIBUTED BY
HEAD OFFICE : 81 Koizumi, Ueda, Nagano, 386-1192, Japan TEL +81-268-28-0562 / FAX +81-268-28-0568 E-mail: os-com@hioki.co.jp HIOKI USA CORPORATION : 6 Corporate Drive, Cranbury, NJ 08512 USA TEL +1-609-409-9109 / FAX +1-609-409-9108 E-mail: hioki@hiokiusa.com
Beijing Office :
A-2602 Freetown, 58 Dong San Huan Nan Road Beijing, P.R.China POSTCODE: 100022 TEL +86-10-5867-4080/4081 FAX +86-10-5867-4090 E-mail: info-bj@hioki.cn
Guangzhou Office :
Room 303, Profit Plaza, No.76, West Huangpu Road Guangzhou, P.R.China POSTCODE: 510623 TEL +86-20-38392673/2676 FAX +86-20-38392679 E-mail: info-gz@hioki.cn 3334E1-7ZM-07P Printed in Japan
All information correct as of Dec. 14, 2007. All specifications are subject to change without notice.